Transformer Oil Filtration Machines: The importance of good quality power makes it very important that all the equipments give their best performance. Transformers being a key equipment, it becomes imperative to maintain optimal insulation properties of the transformer oils by rigid control over moisture, dissolved gases and particulate contamination. Failing in this results in considerable decrease in its BREAK DOWN VOLTAGE, INSULATION RESISTANCE, and increase in DIELECRIC LOSS FACTOR, leading to breakdowns of transformers. Conditioning saves the cost of using new oil frequently and also increases the life of the transformer. Filtration Eliminates
- Solid impurities
- Dissolved water
- Dissolved gases
Engineered to meet your needs Fowler Westrup (India) Private Limited takes pride in its ability to provide equipment specifically designed to meet customer requirements and specifications at reasonable cost.
Customer Service
- Installation
- Commissioning
- Complete Turnkey Applications
- Spare Parts
- Service And Maintenance Schemes
- Technical Support Network
Key Features
- User Friendly
- Easily Replaceable Non-Hygroscopic Filter Cartridges âââ‰â¬Å 1 Micron (nominal)
- Efficient Level Control and Temperature Control Systems
- Most efficient Degassing System
- Minimal Maintenance
- Fail proof Interlocking System
- Fuseless control panel
- Optical level monitor controls the oil and foam level in the degassing chamber
- 3 piece valves with Teflon seating and stainless steel balls
- Slim seal butterfly valves with nylon coated disc
- The oil and vacuum connections are in the form of flanged joints with 'O' Rings, ensuring full sealing efficiency at all times and thus minimal maintenance requirements
Optional
- Transformer Evacuation System
- Hot Oil Circulation / On-site Drying
- Filters Press, Ionic Reaction Column
- Flow meter
- Gas & Moisture Measuring Instruments
- Condensers
- Audio / Visual annunciation
Oil Conditioning Machines Technical Parameters
|
Description Models
|
JMHV
|
JHV
|
JHVR
|
|
Vacuum Level at Final Oil Run Through (in torr)
|
<3
|
< 1
|
< 0.5
|
|
Unprocessed Oil Quality
|
|
Water content (Max.) ppm
|
50
|
50
|
50
|
|
Gas content (Max.) % vol.
|
10
|
10
|
10
|
|
Break down voltage kV
|
20
|
20
|
20
|
|
Oil Quality After Single Pass
|
|
Water content (Max.) ppm
|
20
|
6
|
3
|
|
Gas content (Max.) % vol.
|
2
|
0.5
|
0.1
|
|
Break down voltage kV
|
50
|
60
|
65
|
|
Oil Quality After Two Passes
|
|
Water content (Max.) ppm
|
10
|
3
|
2
|
|
Gas content (Max.) % vol.
|
1
|
0.1
|
0.05
|
|
Break down voltage kV
|
60
|
70
|
7
|
|